Description
The Chiller CSC-5 from CSrental is equipped with environmentally friendly technology that ensures maximum efficiency with minimal electricity consumption and meets the latest technical requirements. By means of pipes and accessories, the CSC chiller can be connected to almost any existing system or process.
The Chiller CSC-5 is standard equipped with a pump and buffer vessel so that installation can be done quickly and easily. Chillers are often used as process coolers or for planned maintenance of existing chillers/coolers.
For temporary climate solutions for business, industry, construction and ATEX environments, CSrental B.V. is the place to be.
CSrental B.V. has professional consultants who can work with you to find the best rental solution for your business.
Call or email us for a customized quote.
Minimum rental period: 7 days
Cooling capacity max. 5.5 kW / +12/7°C
Air flow rate1.500 m³/h
Water flow 0.9 m³/h
Available pressure 252 kPa
Tank capacity 40 L
Coupling 1” Geka
Max. power consumption13 A
Power consumption 2.5 kW
Connection voltage 230V / 50Hz
IP class 54
Noise level 51 dB(A) (at 10 m)
Dimensions L x W x H 700 mm x 600 mm x 960 mm
Weight 90 kg excluding liquids
Mobility Forklift
Water quality requirements
When using water as a secondary fluid, the quality of the water must meet the requirements specified in the table below.
Parameter | Value |
pH | Between 7 – 9 |
Electrical conductivity | 100 – 700 µS/cm |
Solphates SO4- | < 100 mg/l |
Bicarbonate HCO3- | < 200 mg/l |
Cloride C1- | < 50 mg/l |
Phosphate PO4 3- | < 2 mg/l |
Carbon dioxide CO² | < 5 mg/l |
Oxigen O2 | < 0,1 mg/l |
Nitrates NO3- | < 5 mg/l |
Ammonia NH3 | Absent |
Hydrogen sulfide H2S | Absent |
Chlorite | Absent |
Free chlorine | < 0,2 mg/l |
The following liquids are strictly prohibited:
– Demineralised water;
– Distilled water;
– Sea water;
– Other liquids that differ from the standard Ethylene/Propylene glycol.