Description
The CSC 130 chiller is equipped with environmentally friendly technology that ensures maximum efficiency with minimal electricity consumption and meets the latest technical requirements. By means of pipes and accessories, the CSC chiller can be connected to almost any existing system or process.
Minimum rental period: 7 days
Cooling capacity at +12 / 6°C max. 130 kW
Internal buffer tank500 L
Coupling 2″ Bauer
Max. power consumption109 A
Power consumption (pump)4 kW
Flow rate(pump)9,4 / 48 m³/u
Connection voltage 400 V / 125 A – 5 pin
Noise level 61,1 dB (at 10 m)
Dimensions L x W x H 3.520 mm x 1.420 mm x 2.510 mm
Weight 1.936 kg excluding liquids
Mobility Forklift / crane
Water quality requirements
When using water as a secondary fluid, the quality of the water must meet the requirements specified in the table below.
Parameter | Value |
pH | Between 7 – 9 |
Electrical conductivity | 100 – 700 µS/cm |
Solphates SO4- | < 100 mg/l |
Bicarbonate HCO3- | < 200 mg/l |
Cloride C1- | < 50 mg/l |
Phosphate PO4 3- | < 2 mg/l |
Carbon dioxide CO² | < 5 mg/l |
Oxigen O2 | < 0,1 mg/l |
Nitrates NO3- | < 5 mg/l |
Ammonia NH3 | Absent |
Hydrogen sulfide H2S | Absent |
Chlorite | Absent |
Free chlorine | < 0,2 mg/l |
The following liquids are strictly prohibited:
– Demineralised water;
– Distilled water;
– Sea water;
– Other liquids that differ from the standard Ethylene/Propylene glycol.