Description
The CSC 300 chiller is equipped with environmentally friendly technology that ensures maximum efficiency with minimal electricity consumption and meets the latest technical requirements. By means of pipes and accessories, the CSC chiller can be connected to almost any existing system or process.
Minimum rental period: 7 days
Cooling capacity at +12 / 6°C max. 300 kW
Internal buffer tankNo
Coupling 4″ Bauer
Max. power consumption240 A
Power consumption (pump)5,5 kW
Flow rate(pump) min. / max.12,5 / 56 m³/u
Connection voltage 400 V / 4 x 120 mm² powerlock
Noise level 56 dB (at 10 m)
Dimensions L x W x H 4.110 mm x 2.230 mm x 2.650 mm
Weight 2.215 kg excluding liquids
Mobility Forklift / crane
Water quality requirements
When using water as a secondary fluid, the quality of the water must meet the requirements specified in the table below.
Parameter | Value |
pH | Between 7 – 9 |
Electrical conductivity | 100 – 700 µS/cm |
Solphates SO4- | < 100 mg/l |
Bicarbonate HCO3- | < 200 mg/l |
Cloride C1- | < 50 mg/l |
Phosphate PO4 3- | < 2 mg/l |
Carbon dioxide CO² | < 5 mg/l |
Oxigen O2 | < 0,1 mg/l |
Nitrates NO3- | < 5 mg/l |
Ammonia NH3 | Absent |
Hydrogen sulfide H2S | Absent |
Chlorite | Absent |
Free chlorine | < 0,2 mg/l |
The following liquids are strictly prohibited:
– Demineralised water;
– Distilled water;
– Sea water;
– Other liquids that differ from the standard Ethylene/Propylene glycol.
Reviews