Description
The Chiller CSC-500 is equipped with environmentally friendly technology that ensures maximum efficiency with minimal electricity consumption and meets the latest technical requirements. By means of pipes and accessories, the Chiller CSC-500 can be connected to almost any existing system or process.
For temporary climate solutions for business, industry, construction and ATEX environments, CSrental B.V. is the place to be.
CSrental B.V. has professional consultants who can work with you to find the best rental solution for your business.
Call or email us for a customized quote.
Minimum rental period: 7 days
Cooling capacity at +12 / 6°C max. 500 kW
Internal buffer tank No
Coupling 4″ Bauer
Max. power consumption 300A
Power consumption (pump)7,5 kW
Flow rate(pump)60 m³/u
Connection voltage 400V / 4 x 185 mm² powerlock
Noise level 59 dB (at 10 m)
Dimensions L x W x H 5.300 mm x 2.250 mm x 2.650 mm
Weight 3.165 kg excluding liquids
Mobility Forklift / crane
Water quality requirements
When using water as a secondary fluid, the quality of the water must meet the requirements specified in the table below.
Parameter | Value |
pH | Between 7 – 9 |
Electrical conductivity | 100 – 700 µS/cm |
Solphates SO4- | < 100 mg/l |
Bicarbonate HCO3- | < 200 mg/l |
Cloride C1- | < 50 mg/l |
Phosphate PO4 3- | < 2 mg/l |
Carbon dioxide CO² | < 5 mg/l |
Oxigen O2 | < 0,1 mg/l |
Nitrates NO3- | < 5 mg/l |
Ammonia NH3 | Absent |
Hydrogen sulfide H2S | Absent |
Chlorite | Absent |
Free chlorine | < 0,2 mg/l |
The following liquids are strictly prohibited:
– Demineralised water;
– Distilled water;
– Sea water;
– Other liquids that differ from the standard Ethylene/Propylene glycol.